RT-1000 Cooling Tower
The RT-1000 cooling tower is an induced draft counterflow cooling tower with a nominal cooling capacity of 800 tons. The air inlet louver section compresses in height for transport on standard single drop trailers and can be easily errected on the job site. Heavy duty, adjustable jacks on each corner make leveling efficient with minimal need for cribbing support. The RT-1000 comes standard with a fouling resistant fill media and low clog water spray nozzels making it well suited for most industrial applications.
Air Delivery Type
Induced Draft
Fan Motor Size
8 x 7.5 HP
Fan Speed Control
Optional
Full Load Amps
100 Amps
Inlet Connection Size (hot)
4 x 12" Flange
Make-up water connection
2" FNPT
Nominal Water Flow
2400 GPM
Outlet Connection Size (cold)
2 x 12" Flange
Volts/Phase/Hz
480/3/60
Height (ft)
10'-3"
Length (ft)
21'-6"
Operating Weight
26,460 lbs
Shipping Weight
14,970 lbs
Substructure Height
3'-6"
Width
11'-11.5"