Perfecting water heat-load tests for colocation data centre performance
Perfecting water heat-load tests for colocation data centre performance
- The challenge
Ensure optimal performance of cooling systems
- The impact
Optimise cooling infrastructure with confidence
- The solution
Switching on to the benefits of electric boilers
Client:Colocation data centre
Location:Germany
Sectors:Data centres
The challenge
Ensure optimal performance of cooling systems
In the fast-paced world of data centres, where efficiency and reliability are paramount, ensuring optimal performance of cooling systems is critical. Data centres rely heavily on chillers to maintain the appropriate temperature for servers and sensitive equipment. Conducting heat-load tests enables the thorough validation of chiller performance under real-world conditions. Our client wanted to conduct a series of water heat-load tests - a crucial procedure for assessing the capacity and effectiveness of cooling infrastructure. They were looking for water cooled load banks to test a brand-new chiller on the roof of their customer’s site.
Technical requirements:
- 1.5 MW capacity
- Water flow: 162m3/h.
- Temperature in: 20°C
- Temperature out: 28°C
As temporary power and temperature control specialists, offering this service in Germany, we readily accepted the challenge.