Get in touch

Contact Us

AG-6 600 Ton Cooling Tower

Modular and Heavy Industrial Rental Cooling Towers

AG-6 600 Ton Cooling Tower - The AG series cooling towers are a modualr cooling tower and are known as the workhorse of the rental cooling tower industry. They can be used independantly or interconnected with multiple AG series cooling towers to achieve any heat load. Each AG series cooling tower has a folding substructure and an access platform. The permanently attached substructure reduces installation time and can be adjusted to either 5 foot or 8 foot elevations. The access platform serves as an elevated walkway to the external sump and control panel. The thermal performance of the GT series cooling towers are CTI Certified and are available in both standard duty and also in the HD version for those dirty water applications.

Key Data

  1. Nominal Capacity
    600 tons
  2. Nominal Water Flow
    1800 GPM
  3. Air Delivery Type
    Forced Draft
  4. Fan Motor Size
    6 x 7.5 horsepower
  5. Fan Speed Control
    Optional
  6. Full Load Amps
    75 Amps
  7. Volts/Phase/Hz
    480/3/60
  8. Inlet Connection Size (hot)
    1 x 12" Flange
  9. Outlet Connection Size (cold)
    1 x 12" Flange
  10. Make-up water connection
    2" FNPT

Physical Data

  1. Height (ft)
    11-0"
  2. Width (ft)
    12-0"
  3. Length (ft)
    22-0"
  4. Substructure Height
    5-0" / 8-0" / 14-0"
  5. Shipping Weight
    15000 lbs
  6. Operating Weight
    23880 lbs

Features

  • Modular Design
  • Elevated Cold Water Basin
  • External Sump
  • Folding/Telescoping Substructure
  • CTI Certification

Benefits

  • Multiple units can be interconnected to form a single cooling tower capable of achieving any capacity
  • The elevated cold water basin makes draining the cold water long distances without the need for additional pumps
  • Sump screens and float valves are accessible external of the tower
  • The substructure design makes installation safer and more efficient
  • CTI Certification ensures users  the thermal capacity capacity is properly represented

Tell us what you need